UL 1685 电缆和光缆的垂直托盘延燃试验和排烟量测试
预览:1083次 发布时间:1083

The UL flame exposure is a vertical-tray fire test for determining values of cable damage height and smoke release from electrical and optical-fiber cables when the cables are subjected to a flaming ignition source. For a cable to be acceptable under the UL test procedure, each of the following is to be exhibited (see 10.1 and 10.2):

a)    The cable char height is to be less than 8 ft, 0 inch (244 cm) when measured from the bottom of the cable tray in accordance with Section 8.

b)    The total smoke released is to be 95 m2 or less.

c)    The peak smoke release rate is to be 0.25 m2/s or less.



更多关于UL 1685测试,请咨询泰思泰克
咨询电话:(86)0512-66315780,(86)0512-66315430
网址:www.testech.com.cn 
邮箱:sales01@testech.com.cn   info@testech.com.cn



上一新闻
下一新闻
电话:+86 400-878-5780 邮箱:sales@testech.com.cn 地址:江苏省苏州市高新区青花路98号2栋
公众号
扫描进入手机站
苏ICP备13030412号-1 版权所有:泰思泰克(苏州)检测仪器科技有限公司
技术支持:启迈科技